小电流接地系统选线方法的灵敏度分析Sensitivity Analysis of Fault Line Detection Method in Small Current Grounded System
廖俊宏;帅红;梁伟;
摘要(Abstract):
分析了现有的多种单相接地故障选线方法,研究基于暂态量的选线方法的灵敏度在CT采样过程中的影响。小电流接地系统的故障暂态信号很有可能被噪声信号覆盖或相互混淆,影响选线的正确性,本文提出在电压形成回路之前加入带通滤波器,利用滤波器除去对选线结果没有影响的工频信号,通过合理选取电流变送器的变比将故障暂态量放大,在保证暂态量的完整性和正确性的同时,提高了选线的可靠性。仿真计算结果表明,该方法可行且适用于实际应用。
关键词(KeyWords): 配电网;单相接地故障;故障选线;选线灵敏度
基金项目(Foundation):
作者(Authors): 廖俊宏;帅红;梁伟;
参考文献(References):
- [1]程路,陈乔夫(Cheng Lu,Chen Qiaofu).小电流接地系统单相接地选线技术综述(A survey on faulty line selection technology for single-phase grounded transmission line in small current neutral grounded system)[J].电网技术(Power System Technology),2009,33(18):219-224.
- [2]Hanninen S,Lehtonen M.Characteristics of earth faults in electrical distribution networks with high impedance earthing[J].Electric Power Systems Research,1998,44(3):155-161.
- [3]桑在中,张慧芬,潘贞存(Sang Zaizhong,Zhang Huifen,Pan Zhencun).用注入法实现小电流接地系统单相接地选线保护(Protection for single phase to earth fault line selection for ungrounded power system by injecting signal)[J].电力系统自动化(Automation of Electric Power Systems),1996,20(2):11-12,35.
- [4]潘贞存,张慧芬,张帆,等(Pan Zhencun,Zhang Huifen,Zhang Fan,et al).信号注入式接地选线定位保护的分析与改进(Analysis and modification of signal injection based fault line selection protection)[J].电力系统自动化(Automation of Electric Power Systems),2007,31(4):71-75.
- [5]曾祥君,尹项根,于永源,等(Zeng Xiangjun,Yin Xianggen,Yu Yongyuan,et al).基于注入变频信号法的经消弧线圈接地系统控制与保护新方法(New methods for control and protection relay in a compensated medium voltage distribution network based on injecting various frequency current)[J].中国电机工程学报(Proceedings of the CSEE),2000,20(1):29-32,36.
- [6]齐郑,杨以涵(Qi Zheng,Yang Yihan).中性点非有效接地系统单相接地选线技术分析(Analysis of technology of fault line selection for single-phase-to-earth faults in neutral point non-effectively grounded system)[J].电力系统自动化(Automation of Electric Power Systems),2004,28(14):1-5.
- [7]薛永端,冯祖仁,徐丙垠(Xue Yongduan,Feng Zuren,Xu Bingyin).中性点非直接接地电网单相接地故障暂态特征分析(Analysis of transient characteristics of signals phase earth fault in non-solidly earthed network)[J].西安交通大学学报(Journal of Xi’an Jiaotong University),2004,38(2):195-199.
- [8]王耀南,霍百林,王辉,等(Wang Yaonan,Huo Bailin,Wang Hui,et al).基于小波包的小电流接地系统故障选线的新判据(Anew criterionforearthfault line selection based on wavelet packets in small current neutral grounding system)[J].中国电机工程学报(Proceedings of the CSEE),2004,24(6):54-58.
- [9]戴剑锋,张艳霞(Dai Jianfeng,Zhang Yanxia).基于多频带分析的自适应配电网故障选线研究(Study on adaptively choosing fault line under single-phase to ground fault based on analysis of multi-frequency bands)[J].中国电机工程学报(Proceedings of the CSEE),2003,23(5):44-47.
- [10]田书,王晓卫,王娟娟(Tian Shu,Wang Xiaowei,Wang Juanjuan).小电流接地系统输电线路故障定位新方法(New method of transmission line fault location for small current grounding system)[J].电力系统及其自动化学报(ProceedingsoftheCSU-EPSA),2011,23(1):52-57.
- [11]贾清泉,刘连光,杨以涵,等(Jia Qingquan,Liu Lianguang,Yang Yihan,et al).应用小波检测故障突变特性实现配电网小电流故障选线保护(Abrupt change detection with wavelet for small current fault relaying)[J].中国电机工程学报(Proceedings of the CSEE),2001,21(10):78-82.
- [12]齐郑,陈炯聪,杨奇逊(Qi Zheng,Chen Jiongcong,Yang Qixun).基于小波变换和LMS自适应滤波器的单相接地选线方法(Selection of single-phase to ground fault line based on wavelet transform and LMS adaptive filter)[J].电力系统自动化(Automation of Electric Power Systems),2004,28(9):58-61.